BT Firepro-Tec® – Fire Resistant Cables

Four core BT Firepro-Tec ENH(BS5839 – PH120 + BS8434-2)
Manufactured in Accordance with BS 7629-1
BT Cables Part No: BTC1898 – BTC1899 – BTC1900 – C1901

Applications
Screened four core Fire Resistant
cable for Building and Industrial
Management Systems

Sector
BT Firepro-TEC®
Standard Fire Alarm Cables

Design
1. Conductor
4 x Plain Annealed Copper wire

2. Insulation
Silicon Rubber blend
Core 1: Blue,
Core 2: Brown
Core 3: Black,
Core 4: Grey

3. Cable Core lay-up
Two twisted wires 10 twists per metre

4. Drain Wire
Tinned Copper wire

Copper/Polyester115% Coverage

6. Sheath Material
Halogen Free Flame-Retardant (HFFR)

Standard Put Up Length
100 and 500 metres

 

BT Firepro-Tec® – Fire Resistant Cables

Two core BT Firepro-Tec UK (BS5839 – PH120 + ANNEX E)
Manufactured in Accordance with BS 7629-1
BT Cables Part No: BTC1841 – BTC1842– BTC1843 – C1844

Applications
Screened two core Fire Resistant
cable for Building and Industrial
Management Systems

Sector
BT Firepro-TEC®
Standard Fire Alarm Cables

Design
1. Conductor
2 x Plain Annealed Copper wire

2. Insulation
Silicon Rubber blend
Core 1: Blue,
Core 2: Brown

3. Cable Core lay-up
Two twisted wires 10 twists
per metre

4. Drain Wire
Tinned Copper wire

5. Screen
Aluminium/Polyester 115%
Coverage

6. Sheath Material
Halogen Free Flame-Retardant
(HFFR)

Standard Put Up Length
100 and 500 metres